Section 10100
ONE HOUR OPERABLE WALL PANELS
PART ONE - GENERAL
1.1 DESCRIPTION
1.1.1 Work Included: Provide all operable wall panels as listed herein, complete,
In-place as shown on the Drawings, and as needed for a complete and proper
Installation.
1.2 QUAUTY ASSURANCE
1.2.1 Standards: Comply with standards specified herein and as listed In Section
01085.
1.2.2 Qualifications of manufacturers: Products used In the work of this section
shall be produced by manufacturers regularly engaged In manufacture of that
particular Item with a history of successful production acceptable to the Architect.
1.2.3 Qualifications of Installers: Use adequate numbers of skilled work- men who
are thoroughly trained and experienced In the necessary crafts and who are
completely familiar with the specified requirements and the methods needed for proper
performance of the work of this section.
1.3 SUBMITTALS
1.3.1 General: Comply with provisions of Section 01300.
1.3.2 Product Data: Within 35 calendar days after the award of the contract,
submit:
(1) Complete materials list of all Items proposed to be furnished and
Installed under this section.
(2) Manufacturer's data required to demonstrate compliance with specified
requirements, and Shop Drawings when required.
(3) 12" x 12" square samples of each Item demonstrating the full range of
colors, patterns and textures available.
(4) Manufacturer's recommended Installation procedures.
ONE HOUR OPERABLE PARTITIONS
10100-1
PART TWO - PRODUCTS
2.1 MATERIALS
2.1.1 Provide Items specified In the schedule of Items, complete, In respect to the
function as Intended.
2.1.2 Fasteners, screws and bolts: Type and size as recommended by the par-
ticular specialties manufacturer for the component and substrate.
PART THREE - EXECUTION
3.1 INSTALLATION
3.1.1 Install Items specified with experienced Journeymen personnel In strict
compliance with drawings, these documents, and the various manufacturer's published
specifications. In every case, the most stringent requirements for Installation shall
govern this work.
3.1.2 Before starting work, notify Architect of any conflicts detrimental to
Installation or operation of Items. Do not work until a clarification Is made by the
Architect.
3.1.3 Anchorage: Provide anchorage devices required to Install the Item and its
appurtenances, complete. Provide anchorage and rough-In frames In ample time when
required to be built In by other trades. Securely fasten wall-mounted Items to solid
backing or blocking.
3.2 SCHEDULE OF ITEMS
3.2.1 The manufacturers listed below set the function and standard of quality for
materials In this section. Other manufacturers conforming to these standards may be
submitted In accordance with the general provisions, and In accordance with Section
01300 of these Specifications.
3.2.2 Products
(1.5) OPERABLE WAll PANELS - 1 HOUR RATED
PRODUCTS
A. PRODUCT shall be Modernfold Acoustl-Seal 900 series Model 931
(500 DR) manufactured by Modernfold and furnished and Installed -*:
by an authorized distributor. Product shall have a U.L Certificate
for compliance with the 1 hour rating.
B. OPERATION shall consist of a series of manually operated, flat
panels, tops supported, with operable floor seals.
ONE HOUR OPERABLE PARTITIONS
10100-2
C. PANEL CONFIGURATION shall be a series of Individual panels
capable of negotiating angular turns or Intersections Including 90
degree turns at l, T, and X Intersections of supporting track.
D. Panels shall be all steel construction, nominal 3" (76) thick In
manufacturer's standard panel widths (48" max., 1219). All panel
framing elements, horizontally and vertically shall be a minimum
16 ga. (1.390) steel. Panel skins shall be a minimum 21 ga. (.838)
steel with electrolytic flash coat zinc finish on bottom sides of
steel sheet to Inhibit rust. Panel skins shall be lock-formed and
welded directly to frames to form a unitized panel for non-racking
rigidity and durability. Panel skins which are adhesive laminated
to frame, or skins not welded directly to steel frame are not
permitted. "Wrap-around" skin/panel construction shall not require
vertical trim on panel faces and shall, with astragal seal, provide
a minimum "groove" appearance at the vertical panel Joints. Panel
cores shall be Insulated as required to meet acoustical
performance and provide rigid backing for skins. Backing shall be
of non-combustible materials.
E. PANEL FINISH shall be factory applied, Class "A" rated material.
Finish shall be wallcoverlng as Indicated In the FINISH SCHEDULE
on the Drawings. Finish material by others coordinated by
manufacturer.
F. WEIGHT of panels shall be 8-12 Ibs./sq. feet (39-59 kg/m )
(average hanging) based on panel size and option selected.
G. SEALS shall be as follows:
a) Vertical sound seal between panels, (astragal), shall be
required In each panel edge and be of a reversible tongue
and groove configuration permitting universal panel
operation. Astragals shall be steel for maximum durability,
and fire resistance. Rigid plastic astragals are not
acceptable. Vertical astragals which lap back over, or are
flush with panel face shall be powder painted to match
facing material, eliminating a defined stripe at each vertical
panel Joint.
b) Horizontal top seals shall be continuous-contact extruded
vinyl bulb shape to prevent acoustical distortion, with pairs
of non--contactlng vinyl fingers. Color - Primer and Paint by
contractor.
ONE HOUR OPERABLE WALL PARTITIONS
10100-3
c) Operable floor seals:
Floor seals shall provide operable travel of 2.5" (64) to
accomodate + .5" (13) - 1.5" (38) of deflection and/or floor
variation.
Downward seal pressure shall assure an acoustical seal and
resist panel movement. Seal shall be operable from either
panel edge to permit multiple panel positioning and reversible
operation, yet provide security when panels are In place.
Operation requiring separate tools or levers, or from one
panel edge only, or the panel face, shall not be permitted.
Exposed operable floor seal channel shall be dark bronze
finish.
H. SUSPENSION SYSTEM:
a) Track shall be a minimum 8ga. (44) roll formed steel, not
extruded aluminum. Static loading of track with brackets at
48" (122) centers, shall show no failure of track or brackets
at 5,000 Ibs. point loading at mid-span. Track shall be
supported by adjustable steel hanger brackets connected to
structural support by pairs of .5" (13) diameter threaded
rods.
b) Track soffit must be all steel for added fire protection and
be Integral, non-removable, factory primed Off White.
Plywood, particle board or aluminum soffits are not
permitted. Track soffit must accommodate terminations of
plenum sound barrier on both sides of track for maximum
sound control.
c) Carriers, two per panel, shall be all steel with precision
ground concentric bearings, permitting panels to traverse "L",
"T" or "X" Intersections without mechanical switching
devices.
d) Carriers shall attach to panels with a shock absorptive
mounting to prevent undue stress to structural, ceiling or
lighting systems due to abusive handling of panels. Non-
steel tired trolleys or trolleys with un-ground bearings will
not be used.
I. ACOUSTICAL PERFORMANCE of the operable wall panel
construction shall have been tested In an Independent acoustical
laboratory on a fully operational 14'-0" (4267) x 9'-0" (2743) unit
In accordance with ASTM E90-75 test procedure, and shall have
attained an acoustical rating of no less than 50.
ONE HOUR OPERABLE WALL PARTITIONS
10100-4
,
J. CHALKBOARDS shall be 48" (1219) high located as Indicated on
architectural drawings. No exposed fasteners shall be permitted.
K. PASS DOOR shall be of the same construction and thickness as
the panels. It shall be equipped with friction latch and flush
pulls for panic operation. Pass door trim shall be factory prime
painted to receive field applied paint. No threshold shall be
required and door shall be equipped with fixed extruded vinyl
floor seals. Door must be 20-mlnute rated for fire protection with
self closing hidden hinges as per finish hardware specification.
INSTALLATION AND EXECUTION:
A. Preparation of opening shall be by Contractor. Any deviation or
site conditions contrary to approved shop drawings shall be called
to the attention of the Architect.
B. Delivery to the Job site shall be coordinated by Contractor.
Proper storage of doors before Installation and continued
protection during and after Installation shall be the responsibility
of the Contractor.
C. Installation shall be by a local Modernfold authorized factory
trained Installer. Installation shall be In accordance with approved
shop drawings and In accordance with ASTM E557-77.
D. Installation shall be guaranteed for one (1) year against defects In
material and workmanship.
E. The complete Installation of the steel operable walls system as
called for, and detailed on the Drawings, shall be provided In
strict accordance with the drawings and manufacturer's standard
printed specifications, Instruction and recommendations.
END OF SECTION
ONE HOUR OPERABLE WAll PARTITIONS
10100-5