HomeMy WebLinkAbout1990/12/10 Board of Appeals & Advisors Agenda Packet (2)
Item 113B (1)
Defmition of EXIT
Exit is a continuOQs and unobstructed means of egress to a public way and
shall include intervening aisles, doors, doorways, corridors, exterior exit baJco-
nies, ramps, stairways, smokeproof enclosures, horizontal exits, exit passage-
ways, exit courts and yards.
Doors/Doorways
- Corridors
Exterior Exit Balconies
Ramps
StaÏ1ways
Smokeproof Enclosures
Horizontal Exits
Exit Passageways
Exi t Courts
Yards
Public Way
Section 3301 (b)
1
Item 113B (2)
BASIC CONCEPTS OF EXITING
· Exits must be provided for
all building occupants
· Occupants must have control
of all elements of the exiting
system
· Once size and number have
been established, they cannot
be reduced
· Once level or degree of fire
safety has been established,
they cannot be reduced
EXITING
Chapter 33
2
-- ---
Item 113B (3)
TABLE NO. 33-A-MINIMUM EGRESS AND ACCESS REQUIREMENTS
. - ~..- ~ ,... MINIMUM OF ACCESS BY
,,- TWO EXITS ~ MEANS OF A
OTHER THAN RAMP OR AN
ELEVATORS ARE ELEVATOR MUST
REQUIRED OCCU· SE PROVIDED
WHERE PANT FOR THE
NUMBER OF LOAD PHYSICALLY
OCCUPANTS IS FACTOR2 HANDICAPPED
USE' AT LEAST (Sq,Ft.) AS INDICATED3
1. Aircraft Hangars
(no repair) 10 500 Yes
2. Auction Rooms 30 7 Yes I
I
3, Assembly Areas, Concen- I
trated Use (wilhout fixed seats) 50 7 Yes" ~
Auditoriums
Churches and Chapels
Dance Floors
Lobby Accessory to
Assembly Occupancy
Lodge Rooms
Reviewing Stands
Stadiums
\\'airing: Area SO 3 YesJ ~
~. Assembly Areas, Less-con·
centrated Use 50 15 Yes': ~ b
Conference Rooms
Dining Rooms
Drinking Establishments
Exhibit Rooms
Gymnasiums
Lounges
Stages
5, Bowling Alley (assume no I
occupant load for bowling lanes) 50 " Yes
I I ,
6, Children's Homes and
Homes for the Aged 6 80 Ycs~
èO I 1'~S'
7 _ Classrooms 50 I
8. Courlrooms 50 40 Yes I
9. Dormitories 10 50 I Yesì
10, Dwellings 10 300 :--10
11. Exercising Rooms 50 50 Yes
12, Garage, Parking 30 200 Yes'
13, Hospitals and Sanitaríums-
Nursing Homes 6 80 Yes
10 200 I Ycs1i1 ,
14. Hotels and Apartments
] 5. Kitchen--Commcrcial 30 èOO :-';0 !
16 Library Rcadinp: Room 50 50 ì'...."J i
30 50 Yo.:-; I
17. Locker Rooms I
18. :">lalls (see Chapter 56) - i - - i
5
Item 113B (4)
--
19. Manufacturing Areas 30 200 Y~s7
20. Mechanical Equipment Room 30 300 r--;\)
21. Nurseries for Children
(Day care) 7 35 Yes
22. Offices .10 100 Yes' I
23. School Shops and Vocational j
Rooms 50 50 Yes
24. Skating Rinks 50 SOon Yes~ I
the ,
,
skating
area;
15 on the
deck
25. Storage and Stock Rooms 30 I 300 "0 I
26. Stores-Retail Sales Rooms
Basement " 30 Yes
Ground Floor 50 30 Yes
Upper Floors 10 60 Yes
27. Swimmmg Pools 50 50 for Yes'
the pool
area:
15 on [he
dl'ck
30 '00 I I
28. Warehouses I :-':0
29. All others 50 100 I
I For additional rrovi~ions on number of cxil\ from Group H <Jnù I ()ccuranclc\ and from
rooms conl<:iining fucl-fired equipment Of cc!luJo...c nitrale. ....cc Seclinns 3320. 3321 and
.1.122, rc\pcctively.
lThis table shall no! be used to dctermine working SpJCC rcquircmcnI\ pcr pcr\on.
'Elevators shall nol be con.\lrucd as providing a required exit.
4Acccss (0 secondary .íJrcas on balconies Of mezzanines may be by stair... onJy. except when
, such secondary areas contain the only avaiJable roilet faciJities.
~Rcvicwíng st<:inds. grandstands, bleachers, and folding and tclcscopic bleachers need not
comply.
hAccess requirements for conference rooms, dining rooms, lounges and exhibit reoms that
arc parI of an officc use shall be the same as requircd for the office u.l,c.
'Access to flt",rs other than that closest to grade may be by slairs only, except when the only
available toilct facilities are on other levels,
r.Whcn the floor closest to the grade offers the s<:tme rrogram\ and activitlcs J.vailJ.bk on
other floors, access to thc O!hcr floors may be by "'[J.lrs only, except whcn the only
available toilet facilities arc on other levcls.
'Acccss to floors othcr than that closest to grade and 10 garages u...cd In connection \\ nh
apartment houses may be by stairs only.
'IISce Section 1214 for access to buildings and facilities In hotels and apJ.f!mcnls.
II See Section 3303 for basement exit requiremcnts.
~; I~Occupant load based upon five persons for each aIlL!', including 15 fcct of runWJY-
6
Item //3B (5)
POSTING OF ROOM CAPACITY
MAXIMUM
OCCUPANT LOAD
108 STANDING
50 DINING
r1 -
CLASSROOM,
ASSEMBLY AREA
OR SIMILAR USE
<-
SIGN REQUIRED FOR ANY ROOM
HA VING AN OCCUPANT LOAD OF 50
OR MORE, WITHOUT FIXED SEATS
USC Section 3302(c)
UFC Section 25.114(a)
7
Item 113B (6)
NUMBER OF EXITS
A MINIMUM OF:
ONE EXIT FROM ANY USABLE PORTION OF A
BUILDING OR ROOM
TWO EXITS WHERE REQUIRED BY TABLE NO. 33-A
TWO EXITS FROM SECOND STORY WHEN OCCUPANT
LOAD > 10 (except individual
dwelling units)
TWO EXITS FROM THIRD STORY
TWO EXITS FROM BASEMENT (except individual
dwelling units, service areas, or
storage and laundry areas <300 sq. ft.)
THREE EXITS FROM EVERY STORY OR PORTION WITH
AN OCCUPANT LOAD OF 501 TO 1000
FOUR EXITS FROM EVERY STORY OR PORTION WITH
AN OCCUPANT LOAD OF 1001 OR MORE
Section 3303(a)
8
Item 113B (7)
This exceptidrY ~ermits two ormore~âwe"ing units in a
basement to have access to only one exit when the
occupant load does not exceed 10.
One exit required ~
AI !:,
Dwelling Dwelling Dwelling ! - Dwelling
-
unit unit unit un!!
100r less 10 or less
occupants occutJants
exit '" exit
- ...... exit exit - ......
¡ ¡ ¡ ¡ -
! ! .
,,' :
.---! ¡- -
I
exit eXit eXit exit
Dwelling Dwelling Dwelling Dwe'ilng
unit unit unit unit
Basement or second story
The exception also permits occupants of dwelling units
on the second story, and in the basement, to have access
to only one exit even though the total occupant load of the
floor exceeds 10.
NUMBER OF EXITS
Section 3303ia), Exception 1
Item //3B (8)
One exit required
/ for third story
maximum of 500
~ square feet and
roof not occupied.'
Individual
dwelling unit
. Can use a combination of usable Ihird floor and Occupied rool as long
as Ihe lofal area does not exceed 500 square feet (R-3 Occupancy only).
EXITS REQUIRED
Section 3303 (a), Exception 3
10
Item 113B (9)
This provision will apply to the second floor level
within an individual dwelling unit no matter what story of the
building it is on, provided that only one exit is required by
Table No. 33-Ä.
r- One .
I ·t Third floor Two exits
I" ex: < 500 square feet required
Individual , from story.
dwelling unit i One Second floor ,
I eXit ,
" , /
I ~ I First floor One . ~
eXit ,
" " ¡
"'
I
lOne t I
" . I exit Second floor , ,
Individual I I I
dwelling unit I "' One
I First floor exit - -.
. I
Exception 3 is similar to Exception 2 but will apply to the
third floor within an individual dwelling unit when it is limited
to 500 square feet or less.
NUMBER OF EXITS
Section 3303 (a), Exceptions 2 and 3
11
Item 113B (0)
Given: 400 occupants per floor
Exits into first floor ~ Exit enclosures---------
,
, 11 2 exits I ~,
-- -;....--
2 exits iJ required I,
required !,
: _JL 2 exits "
" ~--
, , :1 required I,
'I
,
600 total occupants ~ ; ¡
" 2 exits I,
3 exits required -~ ~-
" ,
~ Ii required II
- - -. il - --
Enclosure
exit
Case 1 Case 2
The number of exits should be determined based upon
the number of occupants that are exiting from a particular
floor. The number of exit enclosures need not be increased
due to the number of occupants within the enclosure.
EXITS REQUIRED
Section 3303 (a)
12
Item 311B (11)
ROOM OR AREA
--
DIAGONAL ~
1/2 DIAGÒNAL
~
--
--
-~
--
---- ~
-- ~
-- -
--- -~
-- -~'
- ~
--- ,
-'
.... - -
~
ARRANGEMENT OF EXITS
Sec. 3303(c)
15
Item 113B (12)
- ~_.- -
Given: Three or more exits required
,
Overall diagonal ~
.......
One-half of overall
diagonal
,'- -
I
~ "~
The location of two of the exits will now be controlled by
one-half the overall diagonal distance. The additional exits
will only be regulated by the "reasonable" distance, which
will be determined by the building official on a case-by-case
basis.
ARRANGEMENT OF EXITS
Section 3303 (c)
16
Item 113B (13)
Open stairway
I
,
~. Open parking garage
\
\
\
\
'-------- ..
~
\ ~ I ]
\ I
\
\
\ 250 feet maximum travel distance
The travel distance in an open parking garage only needs
to be measured to the exit stairway. This will also apply
when the stairway is unenclosed per Section 3309 (a),
Exception 3 or when enclosed with glazing per Section
3309 (b).
DISTANCE TO EXITS
Section 3303 (d)
23
Item 113B (14)
EXITS THROUGH
ADJOINING ROOMS
exit corridor, exit enclosure
or egress from the building t
.... .-
ADJOINING OR
INTERVENING ROOM .-
.
exit corridor, exit enclosure
or egress from the building t
more than ADJOINING OR .-
one exit
required INTERVENING ROOM
from room .-
....
.
EXITS REQUIRED
Section 3303(e)
24
Item 113B (15)
~)(ITS THROUGH
ADJOINING ROOMS
exit corridor, exit enclosure
or egress from the building t
.- exiting not
permitted
KITCHEN,
STORE ROOM,
REST ROOM,
CLOSET OR
SIMILAR
SPACE
.
exit corridor, exit enclosure
or egress from the building t
- .-
ADJOINING OR
INTERVENING ROOM
FOYER, LOBBY .-
OR RECEPTION .-
RX)'.1
(constructed
as required
for corridors)
.
EXITS REQUIRED
Section 3303(e)
25
Item 113B (16)
EXITS THROUGH
ADJOINING ROOMS
exit corridor, exit enclosure
t or egress from tht' building
I ~.J
~ ..- Occupant Load
of 10 or less
ADJOINING OR t
INTERVENING ROOM t
I t
.
-ÞO t ~
{ OCCUPANT LOAD OF }
-ÞO EACH ADJACENT ROOM ~
IS 10 OR LESS
-ÞO ~
.
ADJOINING OR
INTERVENING ROOM
... exit corridor, exit enclosure .
or egress from the building
EXITS REQUIRED
Section 3303(e), Exception 2
26
I tern 113B (17)
'''-
6'S" MINIMUM
~
HANDRAIL
Sec. 3306()
-./ 9"
l MINIMUM RUN
4" MIN. RISE
8" MAXIMUM RISE
OCCUPANT LOAD LESS THAN 10
(Private Stairway)
6'S" MINIMUM
MAXMIMUM TREAD RUN HEADROOM .
VARIATION OF 3/8 INCH
MAXIMUM RISER V ARIA TION HANDRAIL
OF 3/8" Sec. 33D6(j)
MINIMUM RUN
4" MIN. RISE
7" MAXIMUM RISE
OCCUPANT LOAD OF 10 OR MORE
STAIRWAYS
Sec. 3306
59
Item 113B (18)
Sloping
Riser height grade
Þ
7 inches maximum -
, ~.
(8 inches maximum
/ for R-3) . Riser may be less
than 4 inches.
Bottom
-
-
~
~ Sloping
grade .
- Slope not to exceed
3 inches in 3 feet of
stairway width.
Top
RISE AND RUN
Section 3306 (c), Exception 2
60
Item 113B (19)
HORIZONTAL EXIT is an exit from one building into another building on
approximately the same level, or through or around a waIl constructed as required
for a two-hour occupancy separation and which completely divides a floor into
two or more separate areas so as to establish an area of refuge affording safety
from fIre or smoke coming from the area from which escape is made.
A HORIZONTAL EXIT MAY BE CONSIDERED AS A
REQUIRED EXIT WHEN CONFORMING TO THE
PROVISIONS OF CHAPTER 33
MINIMUM 1 1/2 HOUR
FIRE ASSEMBLY þo
TWO-HOUR FIRE- AREA B
RESISTIVE WALL þo
AREA A
A HORIZONTAL EXIT SHALL NOT SERVE AS THE
ONLY EXIT FROM A PORTION OF A BUILDING·
WHEN TWO OR MORE EXITS ARE REQUIRED, NOT
MORE T:AN ONE HALF OF THE TOTAL NUMBER
OF EXITS OR TOTAL EXIT WIDTH MAY BE .
HORIZONTAL EXITS
HORIZONTAL EXITS
Section 3308
3
Item 113B (20)
. "'.-- _~..,... 1· . .'......' .,;..~.....
- -
. DOOR SWING
AREA A
AREA B
TWO-HOUR FIRE-
RESISTIVE WALL
Note: If occupant load >50,
two doors must swing
in direction of exit travel.
AREA E AREA C
THREE EXITS TWO EXITS
REQUIRED REQUIRED
ONE EXIT
REQUIRED
~ TWO-HOUR FIRE-
RESISTIVE WALL
HORIZONTAL EXITS
Section 3308
4
Item 113B (21)
DI~ø.RClE!ÄÆAS
Horizontal exit capacity is based on net clear floor area,
General: 3 sq. ft./occ.
1-1 ambulatory: 15 sq. ft.locc.
1-1 nonambulatory: 30 sq. ft./occ.
A 8
NOTE: Exils for -A" adequate to '/;
meet 1he provisions of Chapter 33 ,/',
but need not include added capacity /',
imposed by occupants entering ;;:;
through horizontal exi1 from "8."
/ E' Horizontal exit Exit ~ _
_- Xlt
. Unlike the provisions of exiting through an adjoining room
the occupant load which exits through a horizontal exit need
not be included when calculating the exit requirements for
the room which is receiving the occupants.
This benefit is based on the fact that by exiting through
the two-hour wall and into a compartment away from the
fire or other hazard, occupants would either be able to
remain in that area until the hazard has been controlled, or
until the orderly use of the remaining exits is possible.
HORIZONTAL EXITS
Section 3308
5
Item //3B (22)
EVERY INTERIOR STAIRWAY, RAMP OR
ESCALATOR SHALL BE ,ENCLOSED AS SPECIFIED
IN SECTION 3309.
.»
\\
EXCEPT:
. In other than Group H and I Occupancies, an
enclosure need not provided for a stairway,
ramp or escalator serving only one adjacent
floor and not connected with corridors or
stairways serving other floors.
. Stairs In R-3 Occupancies and stairs within
individual dwelling units of R-1 Occupancies
need not be enclosed.
. Stairs in open parking garages
ST AIRWAYS ENCLOSURES
Section 3309(a)
6
Item 113B (23)
.>~, . _. < . ". : r:::"". "_' ~ ,. -'~. \' , ç-" .- '. "'
--- ~-MEeHANLCAL :VENTlLA TION_'
IN A SMOKEPROOF ENCLOSURE WITH MECHANICAL
VENTILATION, THE FOLLOWING REQUIREMENTS MUST
BE ADDRESSED:
· Doors
· Vestibule size
· Vestibule ventilation
· Smoke trap
· Stair shaft air movement system
· Operation of ventilating equipment
· Standby power
· Acceptance testing
· Emergency lighting
44"MIN.
6"MAX
CEILING
EXHAUST
z SMOKE l DUCT
'" TRAP
b 20NE
N
~MUSTNOT8E
BELOW SMOKETRAP
6" MAX,
SUPPLY
DUCT.
:%'
CROSS SECTION OF VESTIBULE
SMOKEPROOFENCLOSURE
Section 3310(9)
17
Item 113B (24)
EXIT COURT is a yard or court providing access to a public way for one or
more required exits.
r'-~
Une
I
,
Exit Court
Exit
Court
t: I
" Exit Court I
~I I
EXIT
PASSAGewAY
EXIT
COURT
EXIT
PASSAGewAY
EXIT CO U RTS
Section 3311
18
-.-.,
Item 113B (25)
A1SlJ;ScSHALl TERMI~ATEJN A:
." H
;; CROSS AISLE -
· FOYER
· EXIT
EXIT --LOBBY
EXIT
00000000 00000000
DO DO Do 00--- - 0 DODD Do 0
00000000 00000000
00000000 EJEJoEJEJEJEJEJ
CROSS AISLE
00000 EJoooEJ EJEJEJEJEJ
EJEJEJEJEJ EJEJEJEJEJ EJEJEJEJEJ
EJEJEJEJEJ EJEJoEJEJ EJEJEJEJEJ
EJEJEJEJEJ EJEJEJEJEJ EJEJEJEJEJ _
IN GROUPS A AND E OCCUPANCIES, AISLES SHALL NOT
HAVE A DEAD END GREATER THAN 20 FEET IN LENGTH
CROSS AISLES
Section 3315(e)
31
Item 113B (26)
BASIC WIDTH OF AISLES
IN AREAS HAVING FIXED SEATS
FOYER
EXIT LEXI~ ,EX/~ y~
V,
a:
UJ
>-
0
LI..
0
I-
-'
UJ
>
AISLE WIDTH AISLE WIDTH <:
a:
36" BASIC 42" BASIC l-
e
+30" TRAVEL +30" TRAVEL 0
UJ 0 ,....
-'
66" TOTAL 72" TOTAL (/) 0
;¡ N UJ
100/5 = 20 -J
!!1
66" 72" 20 x 1.5" = 30" 72" <:
(/)
(/)
0
a:
u
0
I-
-J
UJ
>
<:
a:
l-
e
0
,....
CROSS AISLEl
( EXIT 8'..9" EXIT ~
. 72" + .5(66") = 105" = 8'-9"
I I 1 OPTIONAL METHOD OF
CALCULATING CROSS AISLE
STAGE [72" + .5(66) + .5(66) + .5(72)]/2 =
[174"]/2 = 67" OR 7' 3"
TOTAL AISLE WIDTH IS DIVIDED
BY 2 SINCE EXITS ARE PROVIDED
AT EACH END OF CROSS AISLE
AND WE ASSUME ONE.HALF OF
THE OCCUPANTS GO EACH WAY.
AISLES
Section 3315
32