HomeMy WebLinkAboutReso 2013-060RESOLUTION NO. 2013-060
RESOLUTION OF THE CITY COUNCIL OF THE CITY OF
CHULA VISTA ADOPTING THE CHULA VISTA CLOTHES
WASHER GRAYWATER PRE-PLUMBING AND STUB-OUT
FOR NEW RESIDENTIAL CONSTRUCTION
WHEREAS, on May 3, 2011 City Council approved Resolution 2011-076 in which City
Council adopted the Climate Adaptation Strategies and approved their implementation; and
WHEREAS, the Implementation Plan for Strategy #4, Local Water Supply and Reuse,
proposed adopting new regulations to incorporate clothes washer graywater plumbing stub-out in
new residential development; and
WHEREAS, staff is presenting to Council an ordinance amending Chapter 15.28 of the
Municipal Code to require all new detached single-family dwellings and duplexes to include a
clothes washer graywater pre-plumbing and outside stub-out; and
WHEREAS, the installation of a stub-out at time of construction greatly facilitates the
use of graywater in residences; and
WHEREAS, in order to facilitate compliance with the requirements and establish
consistency in the installation and inspection of these requirements, staff developed technical
installation requirements, Chula Vista Clothes Washer Graywater Pre-Plumbing and Stub-Out
for New Residential Construction (attached as Exhibit "A"); and
WHEREAS, the Boazd of Appeals and Advisors, at their January 14, 2013 meeting
recommended that City Council adopt the installation requirements.
NOW, THEREFORE, BE IT RESOLVED by the City Council of the City of Chula Vista
that it hereby adopts the Chula Vista Clothes Washer Graywater Pre-Plumbing and Stub-Out for
New Residential Construction, attached as Exhibit "A," as the installation requirements in the
City of Chula V ista.
Presented by Approved as to form by
Gary albe , P. ., AICP en R. ogins ~~
Assistant C~ y Manager/Director of ~t Attorney \ j
Development Services ~-/
Resolution No. 2013-060
Page No. 2
PASSED, APPROVED, and ADOPTED by the City Council of the City of Chula Vista,
California, this 23rd day of Apri12013 by the following vote:
AYES: Councilmembers: Aguilar, Bensoussan, Ramirez, Salas and Cox
NAYS: Councilmembers: None
ABSENT: Councilmembers: None
Cheryl Cox, M or
ATTEST:
Donna R. Norris, CMC, City Clerk
STATE OF CALIFORNIA
COUNTY OF SAN DIEGO
CITY OF CHULA VISTA
I, Donna R. Norris, City Clerk of Chula Vista, California, do hereby certify that the foregoing
Resolution No. 2013-060 was duly passed, approved, and adopted by the City Council at a
regular meeting of the Chula Vista City Council held on the 23rd day of Apri12013.
Executed this 23rd day of Apri12013.
-L i 1C b/Y fl~lLf/U
Donna R. Norris, CMC, City Clerk
Resolution No. 2013-060
Page No. 3
EXHIBIT A
~V //
~~ Clothes Washer Graywater Pre-Plumbing and
~ ~tvls~ Stub-Out for New Residential Construction
These requirements, or an equivalent alternate method and/or material
approved by the Building Official, are applicable in all new detached single
family dwellings and duplexes.
There aze two basic approaches to installing the pre-plumbing and stub-out for a future clothes
washer graywater system in newly constructed dwelling units. Both methods are installed
adjacent to the regular clothes washer standpipe to allow the clothes washer to drain into the
regulaz sewer standpipe (leading to the building sewer) or be diverted to a gaywater stub-out on
the exterior of the building. The following are the two methods: -
Configuration #1 involves a separate graywater standpipe installed adjacent io the regular
clothes washer standpipe. This can be done by installing an additional outlet box dedicated for
the graywater standpipe. The following installation requirements apply:
The standpipe shall be vented (an air admittance valve is acceptable) and trapped, and all
plumbing materials shall be 2-inch in size.
The standpipe shall have a 2-inch overflow pipe leading downward to the regular washer
sewer standpipe.
• The graywater standpipe outlet box shall be as close as possible to the sewer standpipe so
that the flexible washing machine wastewater dischazge pipe can be manually moved
between the two outlet box drainage pipes to either flow into the sewer or to a future
graywa[er system attached to the stub-out.
The plumbing system must Dave a minimum `/." per foot slope towards the exterior stub-
out.
Configuration #2 uses a 3-Way Diver[er Valve connected to the end of the flexible washing
machine wastewater discharge pipe. The valve position directs the graywater to either the
regulaz standpipe leading to the sewer or to the grayv.~ater sub-out. The following installation
requirements apply:
• The diverter valve and all additional phunbing materials shall be minimum t-inch in size
or greater.
• The graywater stub-out shall have a vacuum breaker installed at [he highest point in the
connection, either inside or outside.
• The diverter valve must be accessible and securely fastened to the interior wall at the
clothes washer.
The followinG General requirements aonly to both configurations:
• Permanent labeling.
o Regular standpipe leading to the building sewer and diverter valve in position to
feed into the sewer standpipe must be permanently labeled "Building Sewer."
rage ~ nf'?
Resolution No. 2013-060
Page No. 4
EXHIBIT A
o Standpipe dedicazed to feed the graywater stub-out and diverter valve in the
position to feed the graywazer stub-out must be permanently labeled "Graywater
to Landscape."
o Exterior graywaier stub-outs must be permanently labeled "GRAYWATER
STUB-OUT. CAUTION- UNSAFE WATER DO NOT DRINK"
o Sections of the graywater piping 5-feet or longer must be labeled "CAUTION:
NON-POTABLE V/ATER, DO NOT DRINK."
An operation and maintenance manual shall be provided. Directions shall indicate the
manual is to remain with the building throughout the life of the system and indicate thaz
upon change of ownership or occupancy, the new owner or tenant shall be notified the
structure contains a graywa[er stub-out or system.
• Stub-out
o Must extend a minimum of 3-inches outward past the exterior wall.
o Must have a rubber cap with a stainless steel tightening draw band to keep it
closed when not conducting graywater. -
o Exterior stub-outs should measure between 18-inches and 48-inches above
finished exterior grade. The higher the better [o assist with the gravity flow of the
system but not to exceed 48" above finished exterior grade.
o The stub-out should be as close to the largest area of landscaping as possible.
• All exterior materials shall be protected firom UV rays by a latex paint, except for the
vacuum breaker device.
• All work and mazetials used shall conform to the California Plumbing Code in effect at
the time of installation.
• Both ends of the graywater stub-out plumbing need to be identified on the plans.
• The graywater plumbing and stub-out is required wherever the clothes washer outlet box
is installed in the building.